Flow velocity determines the plan.

Cleansol calculates the flow required for each pipe size, deploys portable non-invasive flowmeters at multiple locations, reads actual velocity live and records the results branch by branch.

Riser B2 / 8 in main 5.6 ft/s TARGET 5.0PASS
Branch B2-04 / 4 in 4.1 ft/s TARGET 6.0RECHECK

ILLUSTRATIVE READINGS. TARGETS ARE SET PER PROJECT DOCUMENTS.

Why It Matters

A pump rating is not a velocity

A flush only works when the water moves fast enough to carry debris out of the system. Because the flow needed changes with pipe diameter, Cleansol reviews the system configuration, calculates the required flow by section and selects the temporary pumping, filtration and sequence around those targets.

A pump rating or one fixed reading does not establish velocity in every diameter, branch, low point and dead leg. Insufficient velocity lets solids settle exactly where they are hardest to find later.

The same flow moves slower in a larger pipe. Each section needs its own target. 2 IN 4 IN 8 IN FASTER SLOWER SLOWEST SAME FLOW, THREE VELOCITIES
At a constant flow rate, velocity drops as diameter grows. Targets are calculated section by section from the project documents.

Planning Sequence

The targets exist before the water moves

Review the system

Configuration, diameters, materials, branches, low points and dead legs, from the project drawings.

Calculate section targets

Required flow for the specified scouring condition in each section, by pipe size.

Select temporary equipment

Pumping, filtration, connections and valve positions chosen to reach the targets.

Establish the flush sequence

Branch order, isolation plan and the measurement points for each stage.

Field Sequence

Meters move with the flush. The pipe is never cut.

During execution, Cleansol deploys portable, non-invasive flowmeters at multiple points across different pipe sizes. The instruments provide live readings without cutting into the piping and can be repositioned from branch to branch as the flush advances. The resulting velocity record provides project-specific evidence for closeout.

Flushing sequence diagram with repositioned clamp-on meters A temporary pump and filtration skid feeds a supply main with three branches. One clamp-on meter stays on the main. A second meter is currently on branch two, was previously on branch one, and moves to branch three next. Meters clamp on without pipe penetration. TEMPORARY PUMP + FILTRATION 8 IN SUPPLY MAIN RETURN B1 / 4 IN B2 / 4 IN B3 / 6 IN M1 5.6 STAYS ON MAIN DONE M2 4.1 READING NOW NEXT CLAMP-ON INSTALLATION. NO PIPE PENETRATION. READINGS RECORDED BRANCH BY BRANCH.
One meter holds the main as a reference while a second repositions through the branch sequence. Both read live, at different pipe sizes, at the same time.
IMAGE: Licensed commercial photo of a clamp-on ultrasonic flowmeter with live display on industrial piping
alt: Clamp-on ultrasonic flowmeter on insulated industrial piping showing a live reading
IMAGE: Licensed commercial photo of chilled water piping of mixed diameters in a mechanical room
alt: Chilled water piping of different diameters in a mechanical room

Closeout Proof

The record your commissioning team actually wants

Location, pipe size, target, measured value, time and disposition, branch by branch. The log below is a redacted sample with placeholder data. The format ships in the CLEANDOC package when flow verification is in scope.

Sample branch flow log. Project data redacted
LocationNominal pipe sizeTargetMeasuredTimestampDisposition
Riser B2, L3 supply8 in5.0 ft/s5.6 ft/s[date] 09:42PASS
Branch B2-044 in6.0 ft/s4.1 ft/s[date] 10:15RECHECK
Branch B2-044 in6.0 ft/s6.3 ft/s[date] 11:05ADJUSTED
Branch B2-054 in6.0 ft/s6.1 ft/s[date] 11:22PASS
AHU-7 coil loop2 in7.0 ft/s7.2 ft/s[date] 11:38PASS
Return header, L18 in5.0 ft/s5.4 ft/s[date] 12:04PASS

What a Reading Changes

Measurement is only useful if it moves the plan

Live readings inform adjustments to pumping, valving, routing and the flushing sequence while the crew is still on the system. A low branch reading is not a note for the report. It is a change order to the flush, executed the same day and rechecked before the sequence moves on.

IndustryPharmaceutical
RegionMid-Atlantic
PhaseShutdown

Measured low velocity, revised execution, verified recheck

Live readings showed two 4 inch branches below the calculated target while the mains were passing. The crew revised valve positions and staged the temporary pumping to isolate the low branches. Rechecks met target the same shift, and the closeout log records the initial reading, the adjustment and the passing recheck.

Technical Boundaries

What governs the targets

Targets and Acceptance

Flow targets, chemistry and acceptance criteria must follow the project specification, system design, metallurgy, equipment limitations and the water-treatment specialist's approved plan. No single universal velocity applies to every system.

Instruments

Instrument application depends on pipe material, diameter, fluid and installation conditions, confirmed during planning. Validated range, calibration practice and accuracy language are provided with the project record.

Next Step

Flushing scope on your project?

Send the drawings, pipe sizes and any specified flow or velocity criteria. If the criteria are not defined yet, that is normal at this stage. We will identify what the plan needs.

We review project inquiries promptly and follow up as quickly as your project timeline allows.